AHRC13/AHRR13 Design Features

SPLIT SYSTEM AIR HANDLING UNIT
HIGH PERFORMANCE AIR HANDLING UNIT WITH AN IMPENETRABLE INTERNAL METAL LINING DESIGN++

  • Circular Cabinet Design of continuous curvature suppresses flow corner singularities and eddies for higher energy efficiency++
  • Insulated double walls in cylindrical and rectangular cabinets reduce energy Losses; sound power level and air leakage rate to ASHRAE standards.
  • Inner sheet metal wall lining prevents airflow contacts with fiberglass insulation and dust particles for high Indoor Air Quality (IAQ)
  • Designed specifically for high IAQ requirements in Homes, Schools, Healthcare facilities and Government/Public Offices.
  • Equipped with Thermostatic Expansion Valve (TXV), Transformer, Time-delay; and direct drive programmable ECM motors for efficient operation
  • Carefully rated heating elements for comfortable room temperatures
  • Direct Expansion coils are designed with rifled tubing, louvered surface and rippled Edge aluminum fins for high energy efficiency
  • Powder-coated pre-painted cabinet for rust-free appearance
  • All copper joints are sweat connections to prevent refrigerant leaks
  • Several electrical knockouts provided for direct access to power supply and low-voltage lines
  • Mounting tracks provide easy installation and removal of evaporator coil
  • Multi-position cabinet installation with support brackets for circular cabinet
  • Removable sliding filter-racks for easy access for installation and removal of air filters
  • Capacity and Efficiency based designs
  • Meet AHRI and ASHRAE Standards and conform to ETL Testing Standards

NOMENCLATURE

AHR C 13 024 A A V 1 1 1 1 00
Product Type Cabinet Configuration Efficiency Unit Capacity Coil Arrangement Series Revision Cabinet Orientation Evaporator Motor Type Refrigerant Type Throttling Device Voltage Heating Size
Product Type
AHR = Air Handling Unit for Residential Split System

Cabinet Configuration
C = Circular
R = Rectangular

Matching Unit Efficiency
(Seasonal Energy Efficiency Rating – SEER)
13 – 13 SEER
14 – Up to 14 SEER
15 – Up to 15 SEER
16 – Up to 16 SEER
17 – Up to 17 SEER
18 – Up to 18 SEER
21 – Up to 21 SEER

Matching Unit Capacity (Nominal)
024 = 2 Tons (24,000 Btu/h)
030 = 2 ½ Tons (30,000 Btu/h)
036 = 3 Tons (36,000 Btu/h)
042 = 3 ½ Tons (42,000 Btu/h)
048 = 4 Tons (48,000 Btu/h)
060 = 5 Tons (60,000 Btu/h)

Coil Arrangement
A = A-Coil
P = Parallel Slabs (Tandem)
C = Circular Coil

Series Revision
A = Revision A (Coil Configuration, etc.)
(Contact Manufacturer)
Cabinet Orientation
V = Vertical
H = Horizontal
M = Multi-Position

Evaporator Motor Type
1 = PSC, GE
2 = ECM, GE

Refrigerant Type
1 = R-410A
2 = R-22

Throttling Device
1 = Thermostatic Expansion Valve (TXV)
2 = Automatic Expansion Valve (AXV)
3 = Orifice (Piston) Expansion Valve

Voltage
1 = 208/230 V, 1Ph., 60 Hz.
2 = 208/230 V, 1Ph., 50 Hz.

Heating Size
00 = No Heat
03 = 3kW
04 = 4kW
05 = 5kW
10 = 10kW
12 = 12.5kW
15 = 15kW
17 = 17.5kW
20 = 20kW
25 = 25kW

 

AIR HANDLING UNIT SPECIFICATIONS

 

MODEL AHRC13024
AHRR13024
AHRC13030
AHRR13030
AHRC13036
AHRR13036
AHRC13042
AHRR13042
AHRC13048
AHRR13048
AHRC13060
AHRR13060
Nominal Cooling Capacity, Btu/h 24,000 30,000 36,000 42,000 48,000 60.000
Evaporator Coil
Refrigerant Type: R-410A R-410A R-410A R-410A R-410A R-410A
TXV Size (A/C & HP): 2 Ton 2 Ton 3 Ton 3 Ton 4 Ton 5 Ton
Coil Model Number (Contact Manufacturer): AH16221636 AH16221636 AH16261636 AH16261636 AH16301636 AH16301636
Total Face Area (Sq.Ft.): 4.89 4.89 5.78 5.78 6.67 6.67
Coil Arrangements:(Contact Manufacturer): A
TANDEM
CIRCULAR
A
TANDEM
CIRCULAR
A
TANDEM
CIRCULAR
A
TANDEM
CIRCULAR
A
TANDEM
CIRCULAR
A
TANDEM
CIRCULAR
Refrigerant Line Set:
Liquid Line Size: 3/8” 3/8” 3/8” 3/8” 3/8” 3/8”
Suction Line Size: 3/4” 3/4” 3/4” 7/8” 7/8” 7/8”
Blower and Motor:
Blower Wheel Width: 7 1/8” 7 1/8” 8” 8” 10 5/8” 10 5/8”
Blower Wheel Diameter: 9 1/2” 9 1/2” 9 1/2” 9 1/2” 12 1/4” 12 1/4”
Housing Discharge: 9 3/16”x10 1/4” 9 3/16”x10 1/4” 10 ½”x11 3/8” 10 ½”x11 3/8” 13 3/16”x13 5/8” 13 3/16”x13 5/8”
Blower Motor, FLA/HP: 3.5/ 1/2 3.5/ 1/2 3.5/ 1/2 3.5/ 1/2 4.6/ 3/4 4.6/ 3/4
Rated Voltage (@60Hz): 208/230 208/230 208/230 208/230 208/230 208/230
SCFM RANGE High-Low:
(i) Nominal Cool/heat: 600-800 700-1000 850-1200 900-1400 900-1600 1400-2000
(ii) Dehumidification: 419-600 419-750 639–900 842-1000 875-1200 1027-1400
Electric Heater, Kw*: 10(36.06/40.0) 12.5(45.07/50) 15(54.09/60) 17.5(63.1/70) 20(72.12/80) 25(90.1/100)
MCA/MOP** 208V
MCA/MOP** 230V
49.5/50
54.4/55(60)
60.7/65(70)
66.9/70
72.0/75 (80)
79.4/80
83.3/85 (90)
91.9/95 (100)
95.9/100
105.8/110
117.0/120(125)
129.4/130(150)
Cabinet Size(AHRCA) AHRC13024 AHRC13030 AHRC13036 AHRC13042 AHRC13048 AHRC13060
Air Discharge Opening: 11” x 15 3/8” 11” x 15 3/8” 11” x 19 1/4” 11” x 19 1/4” 13 1/2″ x 22” 13 1/2″ x 22”
Cabinet Diameter 27 1/2” 27 1/2” 27 1/2” 27 1/2” 27 1/2” & 33” 27 1/2” & 33”
Cabinet Height 49 1/4” 49 1/4” 53 1/4” 53 1/4” 59 7/8” 59 7/8”
Installed/Shipping Weight 206/221 206/221 234/249 234/249 300/320 300/320
Cabinet Size(AHRRA): AHRR13024 AHRR13030 AHRR13036 AHRR13042 AHRR13048 AHRR13060
Air Discharge Opening 11” x 15 3/8” 11” x 15 3/8” 11” x 19 1/4” 11” x 19 1/4” 13 1/2″ x 22” 13 1/2″ x 22”
Cabinet Length (Side) 21” 21” 21” 21” 21 7/8” 21 7/8”
Cabinet Width (Front) 22” 22” 22” 22” 25 1/2” 25 1/2”
Cabinet Height 49 1/4” 49 1/4” 53 1/4” 53 1/4” 59 7/8” 59 7/8”
Installed/Shipping Weight 165/177 165/177 200/215 200/215 260/277 260/277

*See heater sizing;
**Min. Circuit Ampacity/Max. Overcurrent Protection (Heater & Blower Motor Amps);
++Subject to Revision

Dimensions

MODEL DIMENSIONS
D H
AHRC13024 27 1/2 49 1/4
AHRC13030 27 1/2 49 1/4
AHRC13036 27 1/2 53 1/4
AHRC13042 27 1/2 53 1/4
AHRC13048 27 ½ &33 59 7/8
AHRC13060 27 ½ &33 59 7/8

 

MODEL DIMENSIONS
L W H
AHRR13024 21 22 49 1/4
AHRR13024 21 22 49 1/4
AHRR13036 21 22 53 1/4
AHRR13042 21 22 53 1/4
AHRR13048 21 7/8 25 1/2 59 7/8
AHRR13060 21 7/8 25 1/2 59 7/8

+Dimensions in inches

SUMMARY OF AHRI 210/240 STANDARD RATINGS

 

OUTDOOR UNIT SERIES INDOOR UNIT SERIES COOLING CAPACITY ENERGY EFFICIENCY INDOOR (CFM)
OUTDOOR UNIT MODEL OUTDOOR COIL MODEL INDOOR UNIT MODEL  INDOOR COIL MODEL TOTAL CAPACITY S.H.R**
EER SEER
CRC13024*1111
CRR13024*1111
CR361002413 AHRC13024***
AHRR13024***
AH16221634
AH16221636+
AH16221638
23720 0.72 11.38 13.20 792
CRC13030*1111
CRR13030*1111
CR361002413 AHRC13030***
AHRR13030***
AH16221634
AH16221636+
AH16221638
28265 0.68 11.24 13.18 1015
CRC13036*1111
CRR13036*1111
CR361052413 AHRC13036***
AHRR13036***
AH16261634
AH16261636+
AH16261638
36159 0.70 11.16 13.33 1211
CRC13042*1111
CRR13042*1111
CR361052414 AHRC13042***
AHRR13042***
AH16261634
AH16261636+
AH16261638
42425 0-72 11.10 13.28 1421
CRC13048*1111
CRR13048*1111
CR401102215 AHRC13048***
AHRR13048***
AH16301634
AH16301636+
AH16301638
48132 0.70 11.19 13.19 1628
CRC13060*1111
CRR13060*1111
CR401102215 AHRC13060***
AHRR13060***
AH16301634
AH16301636+
AH16301638
60021 0.69 11.09 13.21 1975

**S.H.R. = Sensible Heat Ratio
+Indoor Coil Used for the Rating
^Energy Efficiency Ratio
^^Seasonal Energy Efficiency Ratio