CRC17/CRR17

17 SEER/2-5 Tons
SPLIT SYSTEM CONDENSING UNIT
24,000-60,000 Btu/h Cooling Capacity

HIGH PERFORMANCE SERIES IIR410A/GREEN PRODUCTSII

DESIGN FEATURES:

  • Oval coil design suppresses flow recirculation, separation and corner singularities for high energy efficiency+
  • R-410A Environment friendly refrigerant
  • Energy-efficient single and two-stage Scroll compressors
  • High performance PSC and ECM motors
  • Rifled copper tube/enhanced aluminum Lanced fin
  • High and low pressure switches for equipment protection
  • Equipped with Emerson Comfort Alert Diagnosis
  • Powdered coated cabinet to prevent rust
  • Easy access to covered and protected service valves
  • Sound level in 70-75 dBA range with compressor blanket
  • Conform to AHRI/ASHRAE Standards
  • Meet Energy-Star ratings

CONDENSING UNIT NOMENCLATURE

 

CR C 17 048 C A 1 1 1 1
Product Type Cabinet Configuration Unit Efficiency Unit Capacity Operating Mode Series Revision Compressor Type Condenser Motor Type Throttling Device Voltage
Product Type
CR = Condensing Unit for Residential Split System

Cabinet Configuration
C = Circular Oval
R = Rectangular

Unit Efficiency
(Seasonal Energy Efficiency Rating – SEER)
13 – 13 SEER
14 – Up to 14 SEER
15 – Up to 15 SEER
16 – Up to 16 SEER
17 – Up to 17 SEER
18 – Up to 18 SEER
21 – Up to 21 SEER

Unit Capacity (Nominal)
024 = 2 Tons (24,000 Btu/h)
030 = 2 ½ Tons (30,000 Btu/h)
036 = 3 Tons (36,000 Btu/h)
042 = 3 ½ Tons (42,000 Btu/h)
048 = 4 Tons (48,000 Btu/h)
060 = 5 Tons (60,000 Btu/h)

Operating Mode
C = Cool Only
H = Heat Pump

Series Revision
Coil Configuration, etc.
(Contact Manufacturer)
Compressor Type
1 – R410 Single Stage (1 Speed) Copeland Scroll Compressor
2 – R410 Two Stage (2 Speeds) Copeland Scroll Compressor
3 – R410 Digital (Variable Speeds) Copeland Scroll Compressor

Condenser Motor Type
1 = PSC, GE
2 = ECM, GE

Throttling Device
1 = Thermostatic Expansion Valve (TXV)
2 = Automatic Expansion Valve (AXV)
3 = Orifice (Piston) Expansion Valve

Voltage Type
1 – 208/230 V, 1 Ph., 60 Hz.
2 – 208/230 V, 1 Ph., 50 Hz.
3 – 208/230 V, 3 Ph., 60 Hz.
4 – 480 V, 3 Ph., 60 Hz.
5 – 460/230 V, 3 Ph., 60 Hz.
6 – 380/415 V, 3 Ph., 50 Hz.
7 – 575V, 3 Ph., 60Hz

CONDENSING UNIT SPECIFICATIONS

MODELS: CRC17024
CRR17024
CRC17030
CRR17030
CRC17036
CRR17036
CRC17042
CRR17042
CRC17048
CRR17048
CRC17060
 CRR17060
UNIT CAPACITY
Nominal Cooling (Btu/h) 24,000 30,000 36,000 42,000 48,000 60,000
SEER(Nominal) 17
Compressor COPELAND SCROLL
RLA 11.7 13.1 15.3 17.9 21.2 27.1
LRA 58.3 73.0 83.0 96.0 104.0 152.9
REFRIGERATION SYSTEM
Refrigerant Type R-410A
Refrigerant Line Set:
Liquid Line Diameter 3/8” 3/8” 3/8” 3/8” 3/8” 3/8”
Suction Line Diameter 3/4” 3/4” 3/4” 7/8” 7/8” 7/8”
Discharge Line Diameter 1/2” 1/2” 1/2” 1/2” 1/2” 1/2”
Throttling Device TXV
TXV Size 2 Ton 2 Ton 3 Ton 3 Ton 4 Ton 5 Ton
Liquid Valve Connection 3/8” 3/8” 3/8” 3/8” 3/8” 3/8”
Suction Valve Connection 3/4” 3/4” 3/4” 7/8” 7/8” 7/8”
Refrigerant Charge++ (lbs.) 6.56 6.68 11.16 11.45 13.20 13.88
CONDENSER FAN MOTOR
Rated HP 1/5:1/3 1/5:1/3 1/5:1/3 1/5:1/3 1/5:1/3 1/5:1/3
RPM, Low/High Speed 632/778 632/778 617/752 617/752 699/815 699/815
Air-flow, Low/High SCFM 2850/3250 2862/3269 2951/3452 2948/3462 3823/4271 3831/4283
Rated FLA 2.80 2.80 2.80 2.80 2.80 2.80
CONDENSER COIL^
Model Number (Contact Manufacturer) CR361102415 CR361102415 CR361102427 CR401102427 CR421102229 CR421102229
Face Area, Sq. Ft. 27.5 27.5 27.25 30.56 32.08 32.08
ELECTRICAL DATA
Voltage/Phase-Hz 208/230/1-60 208/230/1-60 208/230/1-60 208/230/1-60 208/230/1-60 208/230/1-60
MCA/MOP** 17.4/25 19.3/30 21.9/35 25.2/40 29.3/50 36.7/60
SOUND POWER (dBA) 70.3/70.7 70.4/71.2 71.2/71.8 72.1/73.3 74.1/74.9 74.8/75.4
MODELS CRC17024 CRC17030 CRC17036 CRC17042 CRC17048 CRC17060
INSTALLED/SHIPPING WEIGHT+ 239/254 239/254 280/295 329/349 341/361 345/365
MODELS CRR17024 CRR17030 CRR17036 CRR17042 CRR17048 CRR17060
INSTALLED/SHIPPING WEIGHT+ 256/271 256/271 301/316 351/371 365/385 369/389

+in lbs.
^ Condenser Coil Configuration (Contact Manufacturer)
++Unit Full Charge includes 25Ft of Liquid and Suction Line Set.
**Minimum Circuit Ampacity/Maximum Overcurrent Protection

DIMENSIONS:

MODELS DIMENSIONS*
L* W* H*
CRC17024 46.60 40.50 36.25
CRR17024 41.25 40.50 36.25
CRC17030 46.60 40.50 36.25
CRR17030 41.25 40.50 36.25
CRC17036 46.60 40.50 36.25
CRR17036 41.25 40.50 36.25
CRC17042 46.60 40.50 40.25
CRR17042 41.25 40.50 40.25
CRC17048 46.60 40.50 42.25
CRR17048 41.25 40.50 42.25
CRC17060 46.60 40.50 42.25
CRR17060 41.25 40.50 42.25

*Inches

AHRI 210/240 STANDARD RATINGS

OUTDOOR UNIT SERIES INDOOR UNIT SERIES COOLING CAPACITY ENERGY EFFICIENCY INDOOR (CFM) HIGH/LOW
OUTDOOR UNIT MODEL OUTDOOR COIL MODEL INDOOR UNIT MODEL  INDOOR COIL MODEL TOTAL CAPACITY S.H.R** EER^ SEER^^
CRC17024*2211
CRR17024*2211
CR361102415 AHRC17024***
AHRR17024***
AH16221634
AH16221636+
AH16221638
25650 0.71 13.12 17.20 825/660
CRC17030*2211
CRR17030*2211
CR361102415 AHRC17030***
AHRR17030***
AH16221634
AH16221636+
AH16221638
32102 0.68 13.30 17.33 920/736
CRC17036*2211
CRR17036*2211
CR361102427 AHRC17036***
AHRR17036***
AH16261634
AH16261636
AH16261638+
38250 0.73 13.28 17.19 1090/872
CRC17042*2211
CRR17042*2211
CR401102427 AHRC17042***
AHRR17042***
AH16261634
AH16261636
AH16261638+
45125 0.72 13.33 17.02 1372/1098
CRC17048*2211
CRR17048*2211
CR421102229 AHRC17048***
AHRR17048***
AH16301634
AH16301636
AH16301638+
50045 0.67 13.54 17.21 1510/1208
CRC17060*2211
CRR17060*2211
CR421102229 AHRC17060***
AHRR17060***
AH16301634
AH16301636
AH16301638+
59996 0.70 13.50 17.15 1895/1516

**S.H.R. = Sensible Heat Ratio
+Indoor Coil Used for the Rating
^Energy Efficiency Ratio
^^Seasonal Energy Efficiency Ratio